| Type |
CS2 |
| Rated current |
(In) |
|
200A |
| Rated insulation voltage |
c.a./AC |
(Ui) |
(V) |
1000 |
| c.c./DC |
(Ui) |
(V) |
1500 |
| Rated thermal current |
(Ith) |
(A) |
200 |
| Rated operational current (le) |
AC-21A/B |
400V |
(A) |
200 |
| 500V |
(A) |
200 |
| 690V |
(A) |
200 |
| AC-22A/B |
400V |
(A) |
200 |
| 500V |
(A) |
200 |
| 690V |
(A) |
200 |
| AC-23A/B |
400V |
(A) |
200 |
| 500V |
(A) |
160 |
| 690V |
(A) |
125 |
| DC-21A/B(1) |
220V |
(A) |
200 |
| 420V |
(A) |
200 |
| 560V |
(A) |
- |
| DC-22A/B(1) |
220V |
(A) |
200 |
| 420V |
(A) |
200 |
| 560V |
(A) |
- |
| DC-23A/B(1) |
220V |
(A) |
200 |
| 420V |
(A) |
200 |
| 560V |
(A) |
- |
| Rated making capacity at 400V AC23 |
(A) |
2000 |
| Rated breaking capacity at 400V AC23 |
(A) |
1600 |
| Short-circuit withstand current 1 sec. |
(kA) |
8 |
| Short-circuit withstand current 0,25 sec |
(kA) |
16 |
| Short-circuit making capacity |
(400V) |
(kA) |
13,5 |
| Rated operational power AC-23A |
(400V) |
(Kw) |
105 |
| Rated fuse short-circuit |
| Back up fuse |
(A) |
200 |
| R.M.S. value |
(kA) |
50 |
| Peak value |
(kA) |
20 |
| Mechanical endurance |
n° |
10000 |
| Electrical endurance |
n° |
2000 |
| Power losses for pole |
(W) |
2,4 |
| Cable section |
mmq |
120 |
| Bars dimension |
mm |
20x5 |
| Change over time |
(I-II o II-I) |
sec |
1,8 |
| Voltage supply DC |
± 10% |
(V) |
12/24 |
| |
min |
(V) |
18 |
| VOltage supply AC |
± 10% |
(V) |
- |
| Power motor consumption |
(A) |
3 |
| Net weight |
3P |
Kg |
5,5 |
| |
4P |
Kg |
6 |