Rated insulation voltage |
Ui |
(V) |
800 |
Impulse withstand voltage |
Uimp |
(kV) |
8 |
Rated thermal current at 40°C |
Ith/Ithe |
(A) |
63 |
Rated operational current Ie |
AC-21A |
415V |
(A) |
63 |
500V |
(A) |
63 |
690V |
(A) |
63 |
AC-22A |
415V |
(A) |
63 |
500V |
(A) |
63 |
690V |
(A) |
40 |
AC-23A |
415V |
(A) |
40 |
500V |
(A) |
40 |
690V |
(A) |
25 |
Rated making capacity at 415V AC23 |
(A) |
400 |
rated breaking capacity at 415V AC23 |
(A) |
320 |
Rated operational power AC23 |
415V |
(kW) |
15 |
500V |
(kW) |
18,5 |
690V |
(kW) |
18,5 |
Short-circuit withstand current 1 sec |
(400V) |
(kA) |
1,1 |
Rated fuse short circuit current |
Back up fuse gG |
(A) |
63 |
R.M.S. value |
(kA) |
20 |
Peak value |
(kA) |
5,7 |
Mechanical endurance |
n. |
50000 |
Electrical endurance |
n. |
3000 |
Power loss per pole |
W |
0,8 |
Cable section |
mmq |
16-25 |
Max terminal torque |
Nm |
2 |
Operation torque |
Nm |
1,6 |
Auxiliary contacts |
(A) |
3 |
Net weight 3 poles |
(Kg) |
0,13 |
Net weight 4 poles |
(Kg) |
0,16 |
Net weight 6 poles |
(Kg) |
0,30 |
Net weight 8 poles |
(Kg) |
0,40 |