Cat. No.
|
17A122CB0
|
|
|
|
Parameters
|
|
|
|
|
|
|
|
|
|
|
Supply Voltage
|
|
|
|
220 - 415 VAC (3 Phase, 3 Wire)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Supply Variation
|
-20% to +15%
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Frequency
|
50/60 Hz
|
|
|
|
|
|
|
Power Consumption (Max.)
|
12 VA
|
|
|
|
|
|
|
|
Trip Type
|
Definite Time
|
|
|
|
|
Tripping Class
|
NA
|
|
|
|
Trip
|
Current Ranges
|
8-24A
|
|
|
|
Thermal Memory
|
NA
|
|
|
|
Settings
|
Phase Reverse Protection
|
Yes / (100 ms Approx.)
|
|
|
|
|
|
|
|
|
Phase Loss
|
70% of Unbalance
|
|
|
|
|
|
|
|
Current unbalance Protection
|
50% of Unbalance
|
|
|
|
|
|
|
|
Underload
|
50%
|
|
|
|
|
|
|
Locked Rotor Protection
|
NA
|
|
|
|
|
|
Number of In-Built CT?s
|
2
|
|
|
|
|
|
|
|
|
|
Reset Mode
|
Auto, Manual
|
|
|
|
|
|
|
Test Function
|
Yes
|
|
|
|
|
|
|
Time
|
Start Time
|
0.2 to 30s
|
|
|
|
|
|
Delay Time
|
0.2 to 10s
|
|
|
|
|
|
Delay
|
Auto Reset Time
|
6 min
|
|
)
|
|
|
|
ON Delay
|
450 ms ( ±50ms )
|
|
|
|
|
|
|
|
Setting Accuracy
|
± 5%
|
|
|
|
|
|
|
|
|
|
Repeat Accuracy
|
± 2%
|
|
|
|
|
|
|
|
|
|
|
Relay Output
|
1 C/O
|
|
|
|
|
|
|
Output
|
Contact Rating
|
5A @ 240 VAC (Resistive)
|
|
|
|
|
|
|
Electrical Life
|
1 x 105
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Mechanical Life
|
1 x 107
|
|
|
|
|
|
|
Utilization
|
Category
|
AC-15
|
Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/1.5 A
|
|
|
|
|
|
LED Indications
|
Separate indications for Phase Asymmetry, Phase Loss & Phase Sequence / Reverse, Power ON, Underload & Overload
|
|
|
Operating Temperature
|
- 10o C to +60o C
|
|
|
|
|
|
|
Storage Temperature
|
- 25o C to +70o C
|
|
|
|
|
|
|
Humidity (Non Condensing)
|
95% (Rh)
|
|
|
|
|
|
|
Enclosure
|
Flame Retardant UL94-V0
|
|
|
|
|
|
|
Dimension (W x H x D) (in mm)
|
110 X 36.5 X 76.8
|
|
|
|
|
|
|
Weight (unpacked) Approx.
|
210 g
|
|
|
|
|
|
|
Mounting
|
Base Mounting
|
|
|
|
|
|
|
Certification
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Degree of Protection
|
IP 20 for Enclosure
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|