current montoring device 220-240 VAC , 3A-9A INVERSE

  • current montoring device 220-240 VAC , 3A-9A INVERSE
اسم الصنف: current montoring device 220-240 VAC , 3A-9A INVERSE
رقم الموديل 1: 17A222CB0
رقم الموديل 2: 0
الفئة: MONITORING DEVICES
العلامة التجارية: GIC

Cat. No. 17A222CB0  
Parameters  
Supply Voltage  220 - 415 VAC (3 Phase, 3 Wire)
Supply Variation -20% to +15% 
Frequency 50/60 Hz
Power Consumption (Max.) 12 VA
      Trip Settings Trip Type Inverse Time  
Tripping Class 10A, 10, 20, 30  
Current Ranges 3 - 9 A  
Thermal Memory Yes  
Phase Reverse Protection Yes / (100 ms Approx.)
Phase Loss 70% of Unbalance
Current unbalance Protection 50% of Unbalance
Underload 40% to 90%  
Locked Rotor Protection 400% of the set value  
Number of In-Built CT?s 2
Reset Mode Auto, Manual
Test Function Yes
  Time Delay Start Time N A  
Delay Time N A  
Auto Reset Time 3-15 min (As per trip class)  
ON Delay 450 ms ( ±50ms )
Setting Accuracy ± 5%
Repeat Accuracy ± 2%
  Output Relay Output 1 C/O
Contact Rating 5A @ 240 VAC (Resistive)
Electrical Life 1 x 105
Mechanical Life 1 x 107
Utilization Category AC - 15 Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/1.5 A
LED Indications Separate indications for Phase Asymmetry, Phase Loss & Phase Sequence / Reverse, Power ON, Underload & Overloa
Operating Temperature Storage Temperature - 10o C to +60o C - 25o C to +70o C
Humidity (Non Condensing) 95% (Rh)
Enclosure Flame Retardant UL94-V0
Dimension (W x H x D) (in mm) 110 X 36.5 X 76.8
Weight (unpacked) Approx. 210 g
Mounting Base Mounting
Certification  
Degree of Protection IP 20 for Enclosure
         

 



متوفر




الكمية
-
+