Type |
CS3P |
Rated current |
(In) |
|
400A |
Rated insulation voltage |
c.a./AC |
(Ui) |
(V) |
1000 |
c.c./DC |
(Ui) |
(V) |
1500 |
Impulse withstand voltage |
(U imp) |
(kV) |
12 |
Rated thermal current |
(Ith) |
(A) |
400 |
Rated operational current (le) |
AC-21A/B |
400V |
(A) |
400 |
500V |
(A) |
400 |
690V |
(A) |
400 |
AC-22A/B |
400V |
(A) |
400 |
500V |
(A) |
400 |
690V |
(A) |
400 |
AC-23A/B |
400V |
(A) |
400 |
500V |
(A) |
315 |
690V |
(A) |
250 |
DC-21A/B(1) |
220V |
(A) |
250/315 |
420V |
(A) |
400 |
560V |
(A) |
400 |
DC-22A/B(1) |
220V |
(A) |
400 |
420V |
(A) |
400 |
560V |
(A) |
400 |
DC-23A/B(1) |
220V |
(A) |
400 |
420V |
(A) |
400 |
560V |
(A) |
400 |
Rated making capacity at 400V AC23 |
(A) |
4000 |
Rated breaking capacity at 400V AC23 |
(A) |
3200 |
Short-circuit withstand current 1 sec. |
(kA) |
13 |
Short-circuit withstand current 0,25 sec |
(kA) |
26 |
Short-circuit making capacity |
(400V) |
(kA) |
26 |
Rated operational power AC-23A |
(400V) |
(Kw) |
210 |
Rated fuse short-circuit |
Back up fuse |
(A) |
400 |
R.M.S. value |
(kA) |
50 |
Peak value |
(kA) |
30 |
Mechanical endurance |
n° |
8000 |
Electrical endurance |
n° |
1500 |
Rated capacitor power at 400V |
kVAR |
180 |
Power losses for pole |
(W) |
9,4 |
Cable section |
mmq |
240 |
Bars dimension |
mm |
2x25x5 |