Type |
VC5F |
Rated current |
800A |
Rated insulation voltage |
c.a./AC |
Ui |
(V) |
1000 |
c.c./DC |
Ui |
(V) |
500 |
Rated thermal current |
Ith |
(A) |
800 |
Impulse withstand voltage |
Uimp |
(kV) |
12 |
Rated operational current |
AC-21A |
400V |
(A) |
800 |
500V |
(A) |
800 |
690V |
(A) |
800 |
AC-22A |
400V |
(A) |
800 |
500V |
(A) |
800 |
690V |
(A) |
800 |
AC-23A |
400V |
(A) |
630 |
500V |
(A) |
500 |
690V |
(A) |
400 |
DC-21A (1) |
48V |
(A) |
800 |
110V |
(A) |
800 |
220V |
(A) |
800 |
400V |
(A) |
630 |
500V |
(A) |
630 |
600V |
(A) |
630 |
DC-22A (1) |
48V |
(A) |
800 |
110V |
(A) |
800 |
220V |
(A) |
800 |
400V |
(A) |
630 |
500V |
(A) |
630 |
600V |
(A) |
630 |
DC-23A (1) |
48V |
(A) |
630 |
110V |
(A) |
500 |
220V |
(A) |
400 |
400V |
(A) |
- |
Rated operational power |
AC-23A |
400V |
(KW) |
420 |
Rated fuse short-circuit current |
Back up fuse |
(A) |
800 |
R.M.S. value |
(kA) |
50 |
Peak value |
(kA) |
40 |
Rated making capacity 420V c.a. cosø 0,35(0,45°) |
(A) |
8000 |
Rated breaking capacity 420V c.a. cosø 0,35(0,45°) |
(A) |
6400 |
Rated making and breakikng capacity DC (230V L/R =15 ms) |
(A) |
2000 |
Rated capacitor power at 400V |
(KVAr) |
370 |
Mechanical endurance |
n° |
4000 |
Elecrtical endurance |
n° |
1000 |
Bars dimension |
(mm) |
2x40x6 |
Cable section |
(mmq) |
2x185 |
Power losses for pole |
(W) |
85,3 |
Operation torque |
(Nm) |
45 |
Net weight |
3P |
(Kg) |
13 |
(1) Two poles in series |
(2) Fuse not considered |